6.5.18 Heating up gradient room model

Line no.
HC1
HC2
HC3
794
1094
1394
The heating up gradient represents the time in minutes the heating system requires to
raise the room temperature by 1 °C. This setting is used to calculate a fictive room
temperature for rooms without room sensor (Room temp 1 model (8742), Room temp 2
model (8772), and Room temp 3 model (8802)).

6.5.19 Raising the Reduced setpoint

This function is used primarily with heating systems that have only little spare capacity
(e.g. low-energy houses). In such cases, the heating up time would be too long at low
outside temperatures. When the Reduced setpoint is increased, the rooms are
prevented from cooling down to extremely low levels, thus shortening the heating up
time when changing to the Comfort setpoint.
800
1000
TR
1400
710
101
1310
712
1012
1312
Figure 26: Raising the reduced setpoint
Line no.
HC1
HC2
HC3
710
1010
1310
712
1012
1312
800
1000
1400
801
1001
1401
8704
User Manual LMS14...
6 The settings in detail
Operating line
Heat up gradient
801
1001
1401
8704
Meaning
TRK
Room temperature Comfort setpoint
TRR
Room temperature Reduced setpoint
TRwA1
Start of Reduced setpoint increase
TRwA2
End of Reduced setpoint increase
TAgem
Composite outside temperature
TR
Room temperature setpoint – heat gains + room influence
157/617
CC1U7471en
07.05.2014