Siemens LMS14 User Manual page 278

Albatros2 boiler management unit
Table of Contents

Advertisement

Sensor for the swimming
pool
Display of actual values
Additional parameters
Display of minimum and maximum values
Additional parameters
Collector sensor measured value correction
Additional parameters
278/617
Building Technologies Division
The swimming pool sensor is always sensor B13. If the solar plant is activated and the
collector sensor or swimming pool sensor is not available (short-circuit or interruption),
the collector pump is switched off and an error message appears.
The temperatures acquired by sensor B6, B3 and B31 are displayed as collector
temperature 1, DHW temperature 1, and DHW temperature 2. The temperature values
of sensor B4 and B41 are displayed as Buffer storage tank temperature 1 and Buffer
storage tank temperature 2. The swimming pool temperature acquired by sensor B13 is
displayed as the Swimming pool temperature.
Line no.
Operating line
8510
Collector temp 1
8830
DHW temp 1
8980
Buffer temp 1
8982
Buffer temp 2
Collector temperature (sensor B6) features a Slave pointer function displayed as
Collector temperature 1 max and Collector temperature 1 min. They show the
maximum and minimum collector temperatures reached. When making a reset, the
values are reset to the current collector temperature.
Line no.
Operating line
8511
Collector temp 1 max
8512
Collector temp 1 min
Readjustm collector sensor (6098) makes it possible to correct the temperature
acquired by sensor B6 by ±20 °C. The correction is linear across the entire measuring
range.
Note!
The temperature value of the Sensor temperature BX input test displays the
uncorrected measured value. The logical temperature value Collector temperature 1
displays the corrected measured value used by the control system.
Line no.
Operating line
6098
Readjustm collector sensor
8510
Collector temp 1
User Manual LMS14...
6 The settings in detail
CC1U7471en
28.01.2015