6.28.8 Parameter setting state

The parameter setting state is not safety-related, but might lead to availability problems.
When transferring parameters from the stick to the LMS14..., lockout is triggered.
When changing the online DD, only start prevention is activated. The user level for the
parameter setting state is filed in the header of the data set.
Stick series number and data set number are stored in the LMS14... for information.
The LMS14... can be reset upon successful and error-free completion of
parameterization.
When setting the parameters, following must be prevented to avoid lockout:
State
Removal of parameter stick
LMS14... with power failure
Reset of LMS14...
Parameterization aborted
(manually or automatically)
Faulty data set
Parameterization of the LMS14... is incomplete and invalid and, for this reason, the unit
must not be reset. With the help of the ACS432, you can try to replace the data set on
the stick by a correctly working data set (complete and matching).
Note!
The LMS14... checks the stick series number and the data set number. This means
that the new data set must be located in the identical storage position on the same
stick. The repaired stick can now be used to repeat the parameter setting procedure.
An error resulting from parameter changes can also be corrected by setting the
parameters via the ACS420 PC software from the same or a higher user level.
Errors resulting from the transfer of the online DD cannot be rectified via the ACS420
PC software.
If the parameter setting state cannot be canceled, the complete EEPROM must be
reprogrammed (e.g. CAPSY) and the unit must be replaced.
It is possible to write a completely new EEPROM file to the LMS14...
Note!
During read or write processes with the stick, parameters must not be changed with
some other tool to prevent inconsistent data sets.
User Manual LMS14...
6 The settings in detail
Action
Repeat parameterization with the same
stick and the same data set
Repeat parameterization with the same
stick and the same data set
Repeat parameterization with the same
stick and the same data set
Repeat parameterization with the same
stick and the same data set
Store data set again on the stick