6.11.3 Setpoints

The controlled boiler temperature setpoint can be limited by Setpoint min and Setpoint
max. These limitations can be considered to be a protective function for the boiler. In
normal operation, minimum limitation of the boiler temperature is the lower limit value
for the controlled boiler temperature setpoint, depending on the boiler's operating
mode. In normal operation, maximum limitation of the boiler temperature is the upper
limit value for the controlled boiler temperature setpoint.
Note!
The setting range of Setpoint min and Setpoint max is limited by Setpoint manual
control.
120 °C
2213
2212
Range of control
Boiler setpoint
2210
2211
8 °C
Normal operating mode
Figure 37: Boiler setpoints
Line no.
Meaning
2210
Setpoint minimum
2211
Setpoint minimum OEM
2212
Setpoint maximum
2213
Setpoint maximum OEM
User Manual LMS14...
6 The settings in detail
CC1U7471en
07.05.2014