Functional Check / Wiring Test; Setpoints And Setpoint Adjustments; Setpoints - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Display values
Purpose
Setting values
Preselected setpoints
per room group
Configuration
Setting values
Siemens
Building Technologies
The Outputs menu shows the state of the operating mode relays:
Main menu > Room group 1...10 > Room operating mode >
Operating line
Operating mode relay
1
Operating mode relay
2
8.3.8

Functional check / wiring test

During the wiring test, the room operating mode outputs of the room groups can be
switched directly, enabling their function to be checked.
Main menu > Commissioning > Wiring test > Outputs
Operating line
Operating mode room
group 1...10
8.4

Setpoints and setpoint adjustments

8.4.1

Setpoints

Specific setpoints can be predefined for operating modes
and
Economy for each room group.
The RXB/RXL room controllers adopt the setpoints only if configuration parameter
"Setpoint priority" has been set to "Yes". In that case, the setpoints locally
adjusted on the RXB/RXL room controller are overwritten by the setpoints of the
room group.
Main menu > Commissioning > Extra configuration > Room group 1...10 >
Operating line
Setpoint priority
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Room group 1...10 > Room temp. setpoint >
Operating line
Economy cooling
setpoint
Precomfort cooling
setpoint
Comfort cooling
setpoint
Comfort heating
setpoint
Precomfort heating
setpoint
Economy heating
setpoint
Central control unit RMB795B
Function block: "Room group"
Current state
Off, On
Off, On
Comments
----, Comfort, Precomfort, Economy, Protection.
Adjustable values / remarks
Yes, no
Range
Precomfort cooling setpoint
... 250 °C
Comfort cooling setpoint ...
economy cooling setpoint
Comfort heating setpoint ...
Precomfort cooling setpoint
Precomfort heating setpoint
... Comfort cooling setpoint
Economy heating setpoint ...
comfort heating setpoint
–50.0 °C... Precomfort
heating setpoint
Comfort,
Precomfort
Factory setting
30 °C
28 °C
24 °C
21 °C
19 °C
15 °C
69 / 144