2.1.5 Status displays

There are eight LED displays on the front panel of the FM 458. They
provide information about its actual operating status and data for
diagnostics.
LED
Color
Status
INTF
red
lit
IF
red
lit
UF
yellow
lit
MF
yellow
lit
CF
yellow
lit
TF
yellow
lit
RUN
green
lit
flashing
STOP
yellow
lit
flashing
Table 2-5
Significance of the LED status displays
2-8
Internal error, user program is not running
Initialization error
For errors, which occur when initializing the system, the user program
doesn't start. Initialization errors due to incorrect modules or modules
which are incorrectly inserted with respect to how they were originally
configured.
User error
The user program runs, user-defined diagnostics event with the
function block USF
Monitoring error
User program runs, low-priority error during initialization which permits
standard operation to start, e.g. missing or discharged buffer battery.
Communications error
User program runs, erroneous configured communications or
erroneous connection to SIMATIC S7 or EMX 448
Task administration error
User program runs, the following error cases are possible:
Cycle error
a task was not able to be completed within the task sampling time.
Task back-up
If the task is not marked as a task to run with the highest priority, and
it must be restarted.
No free local buffer
The data buffer is no longer enabled. Task start is bypassed.
Software Watchdog
if the basic sampling time is not processed four times one after the
other. The basic clock cycle timer is re-initialized with the configured
basic sampling time and processing continued.
RUN condition
User program runs, the module operates normally also if UF, MF, CF
or TF = "lit"
Initialization running
STOP status
User program is not running, module is in the stop condition, e.g. or
fatal system-, initialization errors or the
S7-CPU is in the stop condition.
Download running in the STOP condition (is faster than the download
in the run condition, which runs in the background)
Significance