Changing the parameter without changing the network
configuration
To change only the created module parameter of the slave station without changing the network configuration, set the
parameter in the following procedure.
1.
Open the "CC IE Field Configuration" window.
For the master/local module QJ71GF11-T2
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/MELSECNET] [CC IE Field Configuration
Setting] button
2.
Select the I/O module in "List of stations" on the "CC IE Field Configuration" window.
(1) List of stations
3.
Open the "Parameter Processing of Slave Station" window.
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
4.
Set "Method selection" to "Parameter read".
5.
Click the [Execute] button and the following window is displayed.
6.
Click the [Yes] button.
(1)
7 VARIOUS SETTINGS
7.2 Changing the Parameter
7