Mitsubishi Electric NZ2GF12A4-16D User Manual Page 127

Cc-link ie field network waterproof/dustproof remote i/o module.
Hide thumbs

Advertisement

Error code
Classification
(hexadecimal)
0101H
Moderate error
0102H
Moderate error
*1
0103H
Moderate error
0104H
Moderate error
0201H
Minor error
*2
0202H
Minor error
0203H
Minor error
*3
0503H
Moderate error
*3
0504H
Moderate error
*3
0506H
Moderate error
Error name
Description and
cause
Non-volatile memory
The module working
error (module working
information stored in the
information)
non-volatile memory are
faulty.
Non-volatile memory
The parameter data
error (parameter)
stored in the non-volatile
memory are faulty.
Power supply voltage
Power supply monitor
error
state flag (RWr3.b0) is
on and the module-and-
sensor power supply or
the load power supply
has a voltage error.
Date out of range error
The clock data acquired
from the CPU module is
incorrect.
Non-volatile memory
The error history data
data error (error history)
stored in the non-volatile
memory are faulty.
Remote buffer memory
Areas other than those
access error
of the remote buffer
memory have been
accessed with the
REMFR/REMTO
instructions.
Station number switch
The station number
changed error
setting switches have
been changed with the
module power on.
Parameter data error
The received parameter
(input OFF delay)
data values are incorrect
or outside the range.
Parameter data error
The received parameter
(cyclic data update
data values are incorrect
watch time setting)
or outside the range.
Parameter data error
The received parameter
(initial operation setting)
data values are incorrect
or outside the range.
Action
• Set Not commanded (0), Commanded (1), and Not
commanded (0) in Module operation information initialization
command (address: 1004H) and set the parameters of the
non-volatile memory to default. Note that number of ON
times integration value will be initialized to zero.
• Take measures against noise with a shielded cable for
connection.
• If this error persists, the module may be in failure. Please
consult your local Mitsubishi representative.
• Set Not commanded (0), Commanded (1), and Not
commanded (0) in Parameter area initialization command
(address: 1002H) and set the parameters of the non-volatile
memory to default.
• Correct the parameter settings.
• Take measures against noise with a shielded cable for
connection.
• If this error persists, the module may be in failure. Please
consult your local Mitsubishi representative.
• Check the setting of Power supply monitor request flag
(RWw3.b0), and wiring of the power supplies, and the status
of each power supply.
• If an error occurs at the startup of the system or when the
system has stopped, correct the timing to turn on or off
Power supply monitor request flag (RWw3.b0).
There may be an influence from noise or a hardware error. If
the same error occurs again even after measures have been
taken against noise, please consult your local Mitsubishi
representative.
• The module will be automatically recovered immediately
after the error occurs. Note that the error history of the errors
that have occurred will be lost.
• Take measures against noise with a shielded cable for
connection.
• If this error persists, the module may be in failure. Please
consult your local Mitsubishi representative.
Correct the setting data of the REMFR/REMTO instruction to
access the remote buffer memory.
Set the switch again to the station number that has been set
before.
■Input module
Check that the value set in Input OFF delay setting X
(address: 0110H to 012FH) is within the setting range (0 to
150000).
■I/O combined module
Check that the value set in Input OFF delay setting X
(address: 0110H to 011FH) is within the setting range (0 to
150000).
Correct the parameter settings.
• Check that the set value in Cyclic data update watch time
setting (address: 0002H) is within the setting range (0 to 20).
Correct the parameter settings.
• Check that the set value in Initial operation setting (address:
0004H) is within the setting range (With initial processing
(0), Without initial processing (1)).
11 TROUBLESHOOTING
11.2 Error Code List