EMC Directive related standards
■Emission requirements
Specifications
Test item
EN61131-2: 2007
CISPR16-2-3
Radiated emission
CISPR16-2-1,
CISPR16-1-2
Conducted emission
*1 QP: Quasi-peak value, Mean: Average value
■Immunity requirements
Specifications
Test item
EN61131-2: 2007
EN61000-4-2
Electrostatic discharge
immunity
EN61000-4-3
Radiated, radio-
frequency,
electromagnetic field
immunity
EN61000-4-4
Electrical fast transient/
burst immunity
EN61000-4-5
Surge immunity
EN61000-4-6
Immunity to conducted
disturbances, induced by
radio-frequency fields
EN61000-4-8
Power-frequency
magnetic field immunity
EN61000-4-11
Voltage dips and
interruption immunity
*1 The accuracy of an analog-digital converter module may temporarily vary within 10%.
External power supply
• Use a CE-marked product for an external power supply and always ground the FG metal fitting. (External power supply
used for the tests conducted by Mitsubishi: TDK-Lambda DLP-120-24-1, IDEC PS5R-SF24, PS5R-F24)
• Use a power cable of 10m or shorter when connecting it to the module power supply terminal.
• Use a power cable of 30m or shorter when connecting it to the load power supply for output part.
Test details
Radio waves from the product are
measured.
Noise from the product to the power
line is measured.
Test details
Immunity test in which electrostatic
is applied to the cabinet of the
equipment.
Immunity test in which electric fields
are irradiated to the product.
Immunity test in which burst noise is
applied to the power line and signal
line.
Immunity test in which lightning
surge is applied to the power line
and signal line.
Immunity test in which high
frequency noise is applied to the
power line and signal line
Immunity test in which the product
is installed in inductive magnetic
field
Immunity test in which power
supply voltage is momentarily
interrupted
Standard value
• 30M-230MHz QP: 40dBV/m (10m in measurement range)
• 230M-1000MHz QP: 47dBV/m (10m in measurement range)
• 150k-500kHz QP: 79dB, Mean: 66dB
• 500k-30MHz QP: 73dB, Mean: 60dB
Standard value
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV CM,
1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
*1
• DC I/O, AC I/O (shielded), analog
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
Appendix 4 EMC and Low Voltage Directives
*1
*1
, communication: 1kV CM