When an LED is connected as a load, the LED lights dimly with the output module off
■Case
The load is operated by leakage current when the output module is off.
Output module
Sink output
Y0
COM-
■Action
Connect a resistor of 5 to 50k in parallel with the LED load.
When a digital display unit is connected as a load, the display may not be normal
■Case
The load is operated by leakage current when the output module is off.
Countermeasure
Output module
Sink output
Y0
CTL+
COM-
■Action
Install a pull-up resistor of 5 to 50k and 0.5 (W) between the outputs of 24VDC power supply and the output module.
Countermeasure
LED
24VDC
Digital display unit
(input signal section)
24VDC
Dedicated IC