Function selection status flag
■Power supply monitor state flag (RWr3.b0)
When the power supply monitoring function is enabled by Power supply monitor request flag (RWw3.b0), this flag is on.
Power supply monitor request
flag (RWw3.b0)
Power supply monitor function
Power supply monitor state
flag (RWr3.b0)
(1) Changed by users
For the power supply monitoring function, refer to the following.
Page 92 Power Supply Monitoring Function
Input X port status
When a short circuit is detected in a set of two sensor power supplies, Input X port status turns on. The LEDs of the two
sensor power supplies of the set in which the short circuit was detected turn on in red.
Input X port status is assigned to each input port for two sensor power supplies.
■Input X port status PS0 to PS7 (RWr4)
b15
b14
b13
b12
0 (fixed)
When PS0 is off: No short circuit has been detected in X0 and X1.
When PS0 is on: A short circuit has been detected in X0 or X1.
When PS1 is off: No short circuit has been detected in X2 and X3.
When PS1 is on: A short circuit has been detected in X2 or X3.
When PS7 is off: No short circuit has been detected in XE and XF.
When PS7 is on: A short circuit has been detected in XE or XF.
*1 The use of these bits is prohibited for the NZ2GF12A42-16DT and NZ2GF12A42-16DTE.
When a short circuit in a set of two sensor power supplies is eliminated and the two sensor power supplies in the port return to
their normal conditions, Input X port status for the port turns off and the LEDs of the two sensor power supplies turn on in
green.
Output Y channel status
When a short circuit is detected in an external device, Output Y channel status turns on. The LED of the output signal in which
the short circuit was detected turns on in red.
■Output Y channel status CS0 to CSF (RWr5)
b15
b14
b13
b12
CSF
CSE
CSD
CSC
When CS0 is off: No short circuit has been detected in Y0.
When CS0 is on: A short circuit has been detected in Y0.
When CS1 is off: No short circuit has been detected in Y1.
When CS1 is on: A short circuit has been detected in Y1.
When CSF is off: No short circuit has been detected in YF.
When CSF is on: A short circuit has been detected in YF.
*1 The use of these bits is prohibited for the NZ2GF12A42-16DT and NZ2GF12A42-16DTE.
When a short circuit in the output signal is eliminated, Output Y channel status for the output signal is turned off and the LED
of the output signal turns on in green.
Controlled by the I/O module
(1)
ON
OFF
Disabled
ON
OFF
b11
b10
b9
b8
b11
b10
b9
b8
CSB
CSA
CS9
CS8
(1)
Enabled
*1
*1
*1
*1
b7
b6
b5
b4
PS7
PS6
PS5
PS4
*1
*1
*1
*1
b7
b6
b5
b4
CS7
CS6
CS5
CS4
Appendix 2 Details of Remote Registers
OFF
Disabled
OFF
b3
b2
b1
b0
PS3
PS2
PS1
PS0
*1
*1
*1
*1
b3
b2
b1
b0
CS3
CS2
CS1
CS0
APPENDICES
A
149

Advertisement

Table of Contents

   Related Manuals for Mitsubishi Electric NZ2GF12A4-16D

Comments to this Manuals

Symbols: 0
Latest comments: