3.2

I/O Module Specifications

Input module

NZ2GF12A4-16D DC input module
Item
Station type
Number of input points
Rated input voltage
Rated input current
Isolation method
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
OFF  ON
Input response time
ON  OFF
Input type
Withstand voltage
Insulation resistance
Protection degree
Wiring method for common
External interface
Module power supply
part
I/O part
Communication part
Applicable waterproof
For power supply
connector
For I/O
Y-branch connector
for I/O
For communications
Cyclic transmission
RX/RY points
RWr/RWw points
Communication cable
Module power supply
Voltage
Current
Short-circuit detection current of sensor power
supply
Weight
The processing time of the remote device station (input) is the time period for internal processing of the
remote device station (input). The value of the processing time of the remote device station (input) is used in
the calculation for the delay time of the cyclic transmission from the remote device station (input) to the master
station (RX/RWr). Calculate the processing time of the remote device station (input) by the following formula.
• The processing time of the remote device station (input) = The input response time + The internal
processing time (0.2ms)
For the delay time of the cyclic transmission from the remote device station (input) to the master station (RX/
RWr), refer to the following.
 User's manual for the master/local module used
3 SPECIFICATIONS
3.2 I/O Module Specifications
NZ2GF12A4-16D
Remote device station
16 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
7mA TYP. (for 24VDC)
Non-isolation
100%
15VDC or more/3.5mA or more
8VDC or less/1.7mA or less
3.3k
0ms/0.5ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Initial setting: 10ms)
Positive common (sink type)
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
IP67
16 points/common (2- to 4-wire, waterproof connector type)
7/8" waterproof connector, 5 pins, male (IN)/female (OUT)
M12 waterproof connector, 5 pins, female, A-code
M12 waterproof connector, 8 pins, female, X-code
Page 14 Recommended Connector List
16 points
12 points
An Ethernet cable that meets the 1000BASE-T standard:
Category 5e or higher (double shielded, STP), straight cable
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
300mA or less (24VDC, all points ON)
400mA or more/input connector
0.72kg