Mitsubishi Electric NZ2GF12A4-16D User Manual page 67

Cc-link ie field network waterproof/dustproof remote i/o module
Table of Contents

Advertisement

Ex.
To set the station to 115, set the switch as shown below.
Setting range
Set the station number from 1 to 120. Setting the value other than 1 to 120 causes a communication error and the D LINK
LED flashes.
• Do not change the station number setting switch while the module is powered on. Changing the station
number setting switch causes a minor error and flashes the ERR. LED. Returning the station number setting
switches to the previous setting eliminates the error after five seconds and turns off the ERR. LED.
• Do not set a station number duplicated with other station numbers. If the station number is duplicated, a
communication error occurs and the D LINK LED does not turn on.
Tightening torque
Tighten the screw for the station number setting switch cover within the following tightening torque range.
Screw type
Station number setting switch cover (M3 screw)
• Do not put oil on the screw. Failure to do so may damage the screw.
• Tighten the screw with an applicable screwdriver. Tightening it with an inapplicable screwdriver may
damage the screw.
Tightening torque range
0.43 to 0.57Nm
6 INSTALLATION AND WIRING
6
65
6.1 Setting Switch

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents