Appendix 2
This section describes details of remote registers for a master/local module.
The described assignment of device numbers assumes that the remote registers of the I/O module are assigned to RWr0 to
RWrB and RWw0 to RWwB.
Module status area
■Initial processing request flag (RWr0.b8)
The operations of Initial processing request flag (RWr0.b8) and Initial processing completion flag (RWw0.b8) vary depending
on the setting value of Initial operation setting (address: 0004H).
• When With initial processing (0) is set
After the module is powered on, Initial processing request flag (RWr0.b8) turns on. Create a program where initial processing
is executed by using Initial processing request flag (RWr0.b8) and Initial processing completion flag (RWw0.b8). When Initial
processing completion flag (RWw0.b8) is turned on, Remote READY (RWr0.b11) turns on. Also when Initial processing
completion flag (RWw0.b8) is turned on, Initial processing request flag (RWr0.b8) turns off.
When setting parameters using Initial processing request flag (RWr0.b8) as an interlock as shown in the
program example, set Initial operation setting (address: 0004H) to With initial processing (0). After that,
perform initial processing and check that Remote READY (RWr0.b11) is on.
For program examples of initial processing, refer to the following.
Page 116 Program example
*1
Module power supply
Initial processing request flag
(RWr0.b8)
Initial processing completion
flag (RWw0.b8)
Parameter area
Remote READY (RWr0.b11)
*2
External input signal X0
RX0
*1 When data link starts at the same time of when the module is powered on
*2 When an external input device connected to X0 is on
(1) Setting values are read from the internal nonvolatile memory.
(2) The operation starts with the setting value A.
APPENDICES

Appendix 2 Details of Remote Registers

Details of Remote Registers
Controlled by the I/O module
Controlled by the program
ON
OFF
ON
OFF
ON
OFF
(1)
OFF
OFF
OFF
OFF
OFF
(Setting value A)
(2)
ON
ON
ON