5
SYSTEM CONFIGURATION
5.1
CC-Link IE Field Network Basic System
Configuration
Configure a network system using modules and partner products supporting CC-Link IE Field Network Basic.
Connect the modules in a star topology using a switching hub and Ethernet cables. Line and ring topologies are not possible.
(1)
(2)
(3)
(1) FX5-ENET (master station)
(2) Hub
(3) External device (remote station)

Access range

The access range of CC-Link IE Field Network Basic is within the same network address of Ethernet. The device connected
beyond the router is not accessible.
Ex.
When the subnet mask is 255.255.255.0 and the network address is 192.168.3.
192.168.3.39
(1)
(3)
192.168.3.1
(1) FX5-ENET (master station)
(2) Hub
(3) External device (remote station)
(4) Router
Use the same subnet mask value and do not assign the same IP address for each remote station.
(3)
(2)
(3)
192.168.3.2
192.168.3.3
Accessible
(3)
(4)
192.168.4.2
(3)
Not accessible
5 SYSTEM CONFIGURATION

5.1 CC-Link IE Field Network Basic System Configuration

5
(3)
61