A load momentarily turns on from off when the system is powered off
■Cause
When an inductive load is connected, [2] Load may turn on from off due to a diversion of back electromotive force at [1]
Shutoff.
Output module
+ Back electromotive force - [3]
Sink output
Y0
ON
Y1
OFF
COM-
CTL+
Output module
- Back electromotive force + [3]
Source output
Y0
ON
Y1
OFF
COM+
CTL-
Load
[2]
Load
[1] Shut off
Load
[2]
Load
[1] Shut off