Download  Print this page

Mitsubishi Electric NZ2GF12A4-16D User Manual Page 129

Cc-link ie field network waterproof/dustproof remote i/o module.
Hide thumbs

Advertisement

Error code list (D000H to DFFFH (D529H and D52BH excluded))
When an error occurs, the ERR. LED does not turn on. The D LINK LED flashes or turns off.
Troubleshoot the problem with the CC-Link IE Field Network diagnostics.
Error code
Classification
(hexadecimal)
D0E0H
Communication
error
D0E1H
Communication
error
D0E2H
Communication
error
D0E3H
Communication
error
D217H
Communication
error
D2A0H
Communication
error
D2A3H
Communication
error
D72AH
Communication
error
DF01H
Communication
error
When multiple errors occur, only the latest error code is stored in Error code (RWr1).
The errors that have occurred in the past can be checked in the error history of the engineering tool.
For error history, refer to the following.
Page 121 Checking by executing a command of the slave station
Page 159 Error history data
Error name
Description and
cause
Station type mismatch
The network parameter
is incorrect or outside
the range.
Own station reserved
The network parameter
is incorrect or outside
the range.
Station No. already in
The station number
use (own station)
switch setting is
incorrect.
Own station No. out of
The network parameter
range
is incorrect or outside
the range.
Transient data command
The transient data
error
request command is
incorrect.
Receive buffer full
The target station is
overloaded and cannot
receive transient data.
Transient data length
The received transient
error
data is incorrect.
Station number switch
A station number out of
out of range
range (a value other
than 1 to 120) has been
set.
Transient data divided
The divided transient
error
data have been
received.
Action
In the network configuration settings of the master station
(submaster station), change the station type to that of the
module.
• In the network configuration settings of the master station
(submaster station), cancel the reserved station setting.
• Change the station number of the module to a station
number that is not reserved.
• Set a unique station number.
• After taking the above action, turn off and on or reset all the
stations where this error has been detected.
Add the station information of the module in the network
configuration settings of the master station (submaster
station).
Correct the request command at the request source, and retry
the operation.
• Check the network status using CC-Link IE Field Network
diagnostics of the engineering tool to take the appropriate
action.
• When the target station is overloaded and cannot receive
transient data, send the data to the target station after a
while.
Correct the number of data (frame length) at the request
source, and retry the operation.
Set the station number within the allowable range.
Send the transient data that is not divided.
11 TROUBLESHOOTING
11.2 Error Code List
11
127

Advertisement

Table of Contents

   Related Manuals for Mitsubishi Electric NZ2GF12A4-16D

Comments to this Manuals

Symbols: 0