NZ2GF12A42-16DTE DC input transistor output module
Item
Station type
Number of input points
Rated input voltage
Rated input current
Isolation method
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
*1
OFF  ON
Input response time
ON  OFF
Input type
Short-circuit detection current of sensor power
supply
Number of output points
Rated load voltage
Max. load current
Isolation method
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
OFF  ON
Output response
*2
time
ON  OFF
Surge suppressor
Output type
Protection function
Overload protection
function
Overheat protection
function
Short-circuit detection current
Withstand voltage
Insulation resistance
Protection degree
Wiring method for common
External interface
Module power supply
part
I/O part
Communication part
Applicable waterproof
For power supply
connector
For I/O
Y-branch connector
for I/O
For communications
Cyclic transmission
RX/RY points
RWr/RWw points
Communication cable
NZ2GF12A42-16DTE
Input specifications
Remote device station
8 points
24VDC (ripple rate: 5% or less) (Allowable voltage
range: 20.4 to 28.8VDC)
7mA TYP. (for 24VDC)
Non-isolation
100%
15VDC or more/3.5mA or more
8VDC or less/1.7mA or less
3.3k
0ms/0.5ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Initial setting: 10ms)
Negative common (source type)
400mA or more/input connector
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
IP67
8 points/common (2- to 4-wire, waterproof connector
type)
7/8" waterproof connector, 5 pins, male (IN)/female (OUT)
M12 waterproof connector, 5 pins, female, A-code
M12 waterproof connector, 8 pins, female, X-code
Page 14 Recommended Connector List
16 points
12 points
An Ethernet cable that meets the 1000BASE-T standard:
Category 5e or higher (double shielded, STP), straight cable
Output specifications
8 points
12/24VDC (ripple rate: 5% or less) (Allowable
voltage range: 10.2 to 28.8VDC)
2A/point, 8A/common
Digital isolator isolation
Current is limited by the overload protection function.
0.1mA or less
0.5VDC (TYP.) 0.5A, 0.8VDC (MAX.) 0.5A
0.5ms or less
1.5ms or less (resistance load)
Zener diode
Source type
Limited current when detecting overcurrent: 6.5A or
more/point
Activated to each point.
Activated to each point.
6.5A or more/point
8 points/common (2-wire, waterproof connector type)