Mitsubishi Electric NZ2GF12A4-16D User Manual Page 87

Cc-link ie field network waterproof/dustproof remote i/o module.
Hide thumbs

Advertisement

Setting procedure
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window  Select an I/O module in "List of stations".  [CC IE Field Configuration] 
[Online]  [Parameter Processing of Slave Station]
2.
Set a delay time for "Input OFF delay setting X".
Setting item
*1
Input OFF delay setting X
*1 Each module has the same item and setting range.
Combination of the input OFF delay function and the fast logic function
Ex.
An application that turns on a lamp for one second or longer responding to a brief turning on of the sensor input on the I/O
combined module
• With the input OFF delay setting, an input signal (X4) turns off after one second (1000000s).
• When the input signal (X4) is on, the output (YA) of the lamp is turned on.
(1) Input signal (X4)
(2) Output (YA)
Item
Input OFF delay setting X4
Fast Logic Setting YA
For the fast logic function, refer to the following.
Page 95 Fast Logic Function
Setting range
• 0 (No delay)
• 1 to 150000 (400s to 60s, 400s unit)
(2)
(1)
Setting
2500
Enable
8 FUNCTIONS
8.2 Input OFF Delay Function
8
85