■Error status flag (RWr0.b10)
Error status flag (RWr0.b10) turns on when a moderate error or major error occurs.
To clear Error code (RWr1), turn on and off Error clear request flag (RWw0.b10)).
• When a moderate error occurs
Error code (RWr1)
Error status flag (RWr0.b10)
Error clear request flag
(RWw0.b10)
Remote READY (RWr0.b11)
(1) An error occurs.
• When a major error occurs
Error code (RWr1)
Error status flag (RWr0.b10)
Error clear request flag
(RWw0.b10)
Remote READY (RWr0.b11)
(1) An error occurs.
(2) When a major error has occurred, the error is not cleared even though an error clear request is issued.
■Error history
The error history is not cleared even if Error clear request flag (RWw0.b10) is turned on and off. To clear the history, set "1" for
Error history clear command (address: 1000H).
For the error history clear, refer to the following.
Page 161 Error history clear command
Controlled by the I/O module
Controlled by the program
(1)
0000H
(Error code)
ON
ON
OFF
Controlled by the I/O module
Controlled by the program
(1)
0000H
ON
ON
OFF
OFF
ON
OFF
(Error code)
(2)
ON
OFF
Appendix 2 Details of Remote Registers
0000H
ON
APPENDICES
147
A