Troubleshooting for output circuit

This section describes the troubleshooting for output circuit.
A load momentarily turns on when the load power supply is powered on
■Cause
An incorrect output occurs due to the stray capacitance (C) between collector and emitter of a photocoupler.
(When a high sensitivity load (such as a solid state relay) is used, this incorrect output may occur.)
Output module
Photocoupler
C
Tr1
Ic
Constant-
voltage circuit
When the load power supply is powered on rapidly, the current (Ic) flows due to the stray capacitance (C).
The current (Ic) flows to the gate of the transistor (Tr1) of the next stage and the output Y0 turns on for approximately 100s.
SW: Load power supply
(24VDC) at On
Output Y0
Y0
Load
CTL+
SW
COM-
24VDC
10ms or less
Approx.100μs