Mitsubishi Electric NZ2GF12A4-16D User Manual page 92

Cc-link ie field network waterproof/dustproof remote i/o module
Table of Contents

Advertisement

Setting procedure
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window  Select an I/O module in "List of stations".  [CC IE Field Configuration] 
[Online]  [Parameter Processing of Slave Station]
2.
Set whether to enable or disable the number of ON times integration function in "Number of ON times integration function
enable".
Item
Number of ON times integration function enable Y
*1 Each module has the same item and setting range.
Checking and clearing the number of ON times
The number of ON times can be checked and cleared on the program.
Item
Number of ON times integration value Y
(address: 0610H to 062FH)
Number of ON times integration value clear
command (address: 1100H)
Number of ON times integration value clear
completed (address: 1101H)
• When the ON time and the OFF time of the target output signal are less than 10ms, the output module
cannot recognize the output change and the number of ON times may not be counted.
• When the number of ON times integration value exceeds 2147483647, the count stops. To integrate the
number of ON times continuously, clear the integration value by using Number of ON times integration value
clear command (address: 1100H).
• The number of ON times is counted also when the fast logic function is enabled.
8 FUNCTIONS
90
8.6 Number of ON Times Integration Function
Setting range
*1
• 0: Disable
• 1: Enable
Description
Stores the integration value of the number of ON times integration
function.
When the corresponding bit of output is turned on, the integration
value for the output with the number of ON times integration function
is cleared to zero.
After the integration value is cleared to zero using Number of ON
times integration value clear command (address: 1100H), the bit of
the output which is cleared to zero turns on.
Reference
Program example
• Page 104 Program Example
Details of Remote Buffer Memory
Addresses
• Page 158 Number of ON times
integration value
Program example
• Page 111 Program example for
clearing the number of ON times
Details of Remote Buffer Memory
Addresses
• Page 164 Number of ON times
integration value clear command
Program example
• Page 111 Program example for
clearing the number of ON times
Details of Remote Buffer Memory
Addresses
• Page 165 Number of ON times
integration value clear completed