Mitsubishi Electric NZ2GF12A4-16D User Manual Page 164

Cc-link ie field network waterproof/dustproof remote i/o module.
Hide thumbs

Advertisement

Parameter area initialization command
Set the parameters stored in a remote buffer memory and nonvolatile memory to the default value.
The module can be restored using this command when Nonvolatile memory data error (parameter) occurs.
b15
b14
b13
b12
0 (fixed)
(1) 0: Not commanded, 1: Commanded
■Remote buffer memory address
Name
Parameter area initialization command
■Operation of the parameter area initialization
When Parameter area initialization command (address: 1002H) is set to Commanded (1), the parameters stored in a
nonvolatile memory is set to the default value.
Parameter of nonvolatile
memory
Parameter area initialization
command (address: 1002H)
Parameter area initialization
completed (address: 1003H)
■Default value
The default value is Not commanded (0).
After the parameters in a nonvolatile memory are set to the default value, the I/O module operates with the
parameters of the default value.
Parameter area initialization completed
This remote buffer memory area shows whether initialization of the parameters stored in a nonvolatile memory is completed
or not.
b15
b14
b13
b12
0 (fixed)
(1) 0: Not performed, 1: Completed
■Remote buffer memory address
Name
Parameter area initialization completed
■Operation of the parameter area initialization
When the initialization of the parameters stored in a nonvolatile memory is completed, Parameter area initialization completed
(address: 1003H) is turned Completed (1).
For the timing of turning the bit to Not performed (0)  Completed (1)  Not performed (0), refer to the following.
Page 162 Parameter area initialization command
■Default value
The default value is Not performed (0).
APPENDICES
Appendix 3 Details of Remote Buffer Memory Addresses
b11
b10
b9
b8
Controlled by the I/O module
Controlled by the program
Set parameter
Not commanded (0)
Not performed (0)
b11
b10
b9
b8
b7
b6
b5
b4
Address
1002H
Commanded (1)
Completed (1)
b7
b6
b5
b4
Address
1003H
b3
b2
b1
Default value
Not commanded (0)
Not performed (0)
b3
b2
b1
b0
(1)
b0
(1)