Mitsubishi Electric NZ2GF12A4-16D User Manual page 162

Cc-link ie field network waterproof/dustproof remote i/o module
Table of Contents

Advertisement

■Error code details
For the following errors, each of additional error information is stored in Error code details  (address: 0A06H to 0A0FH)
*1 The following table describes Error code details  for Error history data 1 (address: 0A00H to 0A0FH).
Error
Error code
Error name
(hexadecimal)
0103H
Power supply voltage
error
0202H
Remote buffer
memory access error
0503H
Parameter data error
(input OFF delay)
0504H
Parameter data error
(cyclic data update
watch time setting)
0506H
Parameter data error
(initial operation
setting)
*2 For the storage data of an error cause, refer to the following.
Page 160 Error history data of when a power supply voltage error occurs
■Error history data of when a power supply voltage error occurs
Information of the module that has detected a power supply voltage error is stored in Error code details 1 of Error history data
 (address: 0A00H to 0AEFH). (The following is an example of Error history data 1 (address: 0A00H to 0A0FH).)
b15
b14
b13
0 (fixed)
(1) 0: The module-and-sensor power supply has no low-voltage error., 1: The module-and-sensor power supply has a low-voltage error.
(2) 0: The module-and-sensor power supply has no overvoltage error., 1: The module-and-sensor power supply has an overvoltage error.
(3) 0: The load power supply has no low-voltage/power-off error., 1: The load power supply has a low-voltage/power-off error.
(4) 0: The load power supply has no overvoltage error., 1: The load power supply has an overvoltage error.
APPENDICES
160
Appendix 3 Details of Remote Buffer Memory Addresses
Information to be stored
Error code details 1
(address: 0A06H)
*2
Error cause
Start address of the
remote buffer memory
specified with REMFR/
REMTO
Remote buffer memory
address of the parameter
in which an error is
detected
(Input OFF delay setting
X (address: 0110H to
012FH))
Remote buffer memory
address of the parameter
in which an error is
detected
(Cyclic data update watch
time setting (address:
0002H))
Remote buffer memory
address of the parameter
in which an error is
detected
(Initial operation setting
(address: 0004H))
b12
b11
b10
b9
Error code details 2
(address: 0A07H)
0 (fixed)
0 (fixed)
The value written to the corresponding address is
stored. Check that the value is within the range of the
input OFF delay setting (0 to 150000).
The value written to the
corresponding address is
stored. Check that the
value is within the range of
the cyclic data update
watch time setting (0 to
20).
The value written to the
corresponding address is
stored.
b8
b7
b6
b5
Error code details 3
Error code details 4
(address: 0A08H)
to Error code
details 10
(address: 0A09H to
0A0FH)
0 (fixed)
0 (fixed)
0 (fixed)
0 (fixed)
0 (fixed)
0 (fixed)
b4
b3
b2
(4)
(3)
*1
.
b1
b0
(2)
(1)