Operation procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module QJ71GF11-T2
Project window  [Parameter]  [Network Parameter]  [Ethernet/CC IE/MELSECNET]  [CC IE Field Configuration
Setting] button
2.
Select the I/O module in "List of stations" on the "CC IE Field Configuration" window.
(1) List of stations
The points of "RWw/RWr Setting" can be increased/decreased in increments of four points. Decreasing the
points of "RWw/RWr Setting" shortens the link refresh time when some remote register areas are not used.
3.
Open the "Parameter Processing of Slave Station" window.
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
4.
Set "Method selection" to "Parameter write".
(1)
7 VARIOUS SETTINGS
7.1 Parameter Setting
7
73