Output Module - Mitsubishi Electric NZ2GF12A4-16D User Manual

Cc-link ie field network waterproof/dustproof remote i/o module.
Hide thumbs

Advertisement

Output module

NZ2GF12A2-16T transistor output module
Item
Station type
Number of output points
Rated load voltage
Max. load current
Isolation method
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
OFF  ON
Output response time
ON  OFF
Surge suppressor
Output type
Withstand voltage
Insulation resistance
Protection degree
Wiring method for common
Protection function
Overload protection
function
Overheat protection
function
External interface
Module power supply
part
I/O part
Communication part
Applicable waterproof
For power supply
connector
For I/O
Y-branch connector
for I/O
For communications
Cyclic transmission
RX/RY points
RWr/RWw points
Communication cable
Module power supply
Voltage
Current
Short-circuit detection current
Weight
The processing time of the remote device station (output) is the time period for internal processing of the
remote device station (output). The value of the processing time of the remote device station (output) is used
in the calculation for the delay time of the cyclic transmission from the master station (RY/RWw) to the remote
device station (output). Calculate the processing time of the remote device station (output) by the following
formula.
• The processing time of the remote device station (output) = The output response time (1.5ms) + The
internal processing time (0.2ms) = 1.7ms
For the delay time of the cyclic transmission from the master station (RY/RWw) to the remote device station
(output), refer to the following.
 User's manual for the master/local module used
3 SPECIFICATIONS
3.2 I/O Module Specifications
NZ2GF12A2-16T
Remote device station
16 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
2A/point, 8A/common
Digital isolator isolation
Current is limited by the overload protection function.
0.1mA or less
0.3VDC (TYP.) 0.5A, 0.6VDC (MAX.) 0.5A
0.5ms or less
1.5ms or less (resistance load)
Zener diode
Sink type
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
IP67
16 points/common (2-wire, waterproof connector type)
Limited current when detecting overcurrent: 6.5A or more/point
Activated to each point.
Activated to each point.
7/8" waterproof connector, 5 pins, male (IN)/female (OUT)
M12 waterproof connector, 5 pins, female, A-code
M12 waterproof connector, 8 pins, female, X-code
Page 14 Recommended Connector List
16 points
12 points
An Ethernet cable that meets the 1000BASE-T standard:
Category 5e or higher (double shielded, STP), straight cable
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
240mA or less (24VDC, all points ON)
6.5A or more/point
0.71kg