Examples Of Troubles With The I/o Module; Troubleshooting For Input Circuit - Mitsubishi Electric NZ2GF12A4-16D User Manual

Cc-link ie field network waterproof/dustproof remote i/o module.
Hide thumbs

Advertisement

11.6

Examples of Troubles with the I/O Module

Troubleshooting for input circuit

This section describes the troubleshooting for input circuit.
An input signal does not turn off No.1
■Cause
Drive by a switch with LED indicator
Leakage current
■Action
Connect an appropriate resistor as shown below so that a current through the input module may become lower than the OFF
current.
Resistor
For the calculation example of a resistor to be connected, refer to the following.
Page 135 Calculation example
11 TROUBLESHOOTING
11.6 Examples of Troubles with the I/O Module
DC input (sink)