GOT side
100 or less
(3.94)
5.2.6
Grounding a cable
■1. Grounding method
Ground the cable and ground cable to the control panel where the GOT and the PLC are installed.
Ground the braided shield section of the cable to the control panel with the cable clamp (AD75CK).
Ground the ground cable to the FG terminal
at the GOT power supply section when using
GT15-C□EXSS-1 or GT15-C□BS.
To ground a bus connection cable, ground the braided cable for grounding to the control panel by tightening a screw.
■2. Precautions
Do not arrange the cable clamp close to the other cables that are not clamped.
The noise from the control panel may enter the cable clamp and adversely affect the GOT.
5 - 18
5.2 EMC Directive Requirements
• Install a ferrite core to the cable in the positions as shown in the figure below.
Ferrite core
(ZCAT3035-1330)
GOT FG terminal
FG wire
Braided shield
Cable clamps
For the attachment details of cable clamps, refer to
AD75CK-type Cable Clamping Instruction Manual
<IB-68682>.
Bus connection cable
PLC CPU side
100 or less
Unit: mm (inch)
(3.94)