■2. GT2512F-S, GT2510F-V, GT2508F-V
When a multimedia unit (GT27-MMR-Z), MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13), or
CC-Link communication unit (GT15-J61BT13) is mounted, the operating ambient temperature must be 5°C lower than
the maximum temperature described in Section 3.1 General Specifications.
(1) Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature
must be within 40 °C.
(2) Installing the GOT vertically
When the GOT is installed a 90° angle, , the control panel inside temperature must be within 55°C.
When the GOT is installed at any angle other than 90°, the control panel inside temperature must be within 40°C.
Display
GOT
section
Control panel
or others
Display
section
GOT
Control panel
or others
6.5 Control Panel Inside Temperature and GOT Installation Angle
105°
60°
90°
6
6 - 29