5.2.4
Connection of power cables and ground cables
Carry out wiring and connect the power and ground cables according to the following instruction.
By the different wiring or connection method, the system may not comply with EMC Directive.
■1. Wiring method
As shown in the figure below, connect the power cable and the ground cable, and then attach a ferrite core
(ZCAT3035-1330, manufactured by TDK Corporation) within the specified range.
GT23 does not need ferrite cores.
Make sure to ground the LG cable and FG cable.
For connection of power cables and ground cables, refer to the following.
➠
5.2.1
GT2705-VTBD, GT25-W, GT21 do not have the LG ground terminal.
(1) 100 V AC to 240 V AC GOT power supply section (GT27, GT25, GT23 only)
(2) 24 V DC GOT power supply section (GT27, GT25, GT23, only)
■2.
Connection of power and ground cables
INPUT
100-240VAC
(LG)
INPUT
24VDC
-
+
(LG)
(FG)
Ferrite core
(ZCAT3035-1330)
(FG)
Ferrite core
(ZCAT3035-1330)
5.2 EMC Directive Requirements
5
5 - 11