Overview; Conforming Standards In The Emc Directive - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

5.1

Overview

For the products sold in European countries, the conformance to the EMC Directive, which is one of the European
Directives, has been a legal obligation since 1996.
In addition, conformance to the Low Voltage Directive, another European Directive, has also been a legal obligation since
1997.
Manufacturers, who recognize that their products comply with the EMC Directive and the Low Voltage Directive, must
declare that their products comply with the Directives and put a CE mark on the products.
■1. Sales representative in Europe
The sales representative in Europe is as shown below.
Company name: Mitsubishi Electric Europe BV
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
5.1.1

Conforming standards in the EMC Directive

The GOT complies with the following standards in the EMC Directive.
Applied
standard
CISPR16-2-3
Radiated noise
CISPR16-2-1
Conducted noise
IEC61000-4-2
Electrostatic immunity
IEC61000-4-3
Radiated electromagnetic field,
amplitude modulation
IEC61000-4-4
EN61131-2
Fast transient burst noise
: 2007
IEC61000-4-5
Surge immunity
IEC61000-4-6
Conducted RF immunity
IEC61000-4-8
Power supply frequency magnetic
field immunity
IEC61000-4-11
EN61131-2
Instantaneous power failure and
: 2007
voltage dips immunity
5 - 2
5.1 Overview
Test standard
Test for measuring electromagnetic
*1*2
emissions from the product
Test for measuring electromagnetic
emissions from the product to the power
*1*2
cables
Immunity test in which static electricity is
*1*2
applied to the cabinet of the equipment
Immunity test in which an electric field is
applied to the product
*1*2
Immunity test in which burst noise is applied
*1*2
to the power cables and the signal lines
Immunity test in which lightening surge is
*1*2
applied to the product
Immunity test in which a noise inducted on
the power cable and the signal lines is
*1*2
applied
Test for checking normal operations under
the circumstance exposed to the
ferromagnetic field noise of the power
*1*2
supply frequency (50/60 Hz)
Test for checking normal operations at
instantaneous power failure
Test details
• 30 MHz to 230 MHz
• 230MHz to 1000MHz
• 150kHz to 500kHz
• 500kHz to 30MHz
• Contact discharge: ±4 kV
• Aerial discharge: ±8 kV
80 MHz to 1000 MHz: 10 V/m
1.4GHz to 2GHz: 3V/m
2.0GHz to 2.7GHz: 1V/m
(80% amplitude modulation at 1 kHz)
Power cable: 2kV
Digital I/O: 1kV
Analog I/O: 1kV
Signal cable: 1kV
• AC power type
• DC power type
Power cable: 10V
Data communication port: 10 V
30 A/m
• AC power type
Standard value
QP: 30 dBμV/m (measured at 30 m)
QP: 37 dBμV/m (measured at 30 m)
*3
QP: 79dB, Mean: 66dB
*3
QP: 73dB, Mean: 60dB
Power cable (between cable and ground):
±2 kV
Power cable (between cables): ±1 kV
Data communication port: ±1 kV
Power cable (between cable and ground):
±0.5kV
Power cable (between cables): ±0.5kV
Data communication port: ±1 kV
0.5 cycle 0% (Interval 1 second to 10
seconds)
250/300 cycle 0%
10/12 cycle 40%
25/30 cycle 70%
*3*4
*3*4

Advertisement

Table of Contents
loading

Table of Contents