6.5.2

GT25-W

Install the GOT with its display section positioned as shown below.
Using the GOT with the installation angle other than the following accelerates the deterioration of the GOT.
■1. GT2510-WX, GT2507-W
(1) Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature
must be within 40 °C.
(2) Installing the GOT vertically
When the GOT is installed a 90° angle, , the control panel inside temperature must be within 55°C.
When the GOT is installed at any angle other than 90°, the control panel inside temperature must be within 40°C.
GOT
Display
section
Control panel
or others
GOT
Display
section
Control panel
or others
6.5 Control Panel Inside Temperature and GOT Installation Angle
105°
60°
90°