FC 300 Design Guide
8.9.2 Use of EMC-Correct Cables
Danfoss recommends braided screened/armoured cables to optimise EMC immunity of the control cables and the EMC emission from the motor cables.
The ability of a cable to reduce the in- and outgoing radiation of electric noise depends on the transfer impedance (Z
designed to reduce the transfer of electric noise; however, a screen with a lower transfer impedance (Z
higher transfer impedance (Z
).
T
Transfer impedance (Z
) is rarely stated by cable manufacturers but it is often possible to estimate transfer impedance (Z
T
design of the cable.
Transfer impedance (Z
) can be assessed on the basis of the following factors:
T
-
The conductibility of the screen material.
-
The contact resistance between the individual screen conductors.
-
The screen coverage, i.e. the physical area of the cable covered by the screen - often stated as a percentage value.
-
Screen type, i.e. braided or twisted pattern.
a.
Aluminium-clad with copper wire.
b.
Twisted copper wire or armoured steel wire cable.
c.
Single-layer braided copper wire with varying percentage screen
coverage.
This is the typical Danfoss reference cable.
d.
Double-layer braided copper wire.
e.
Twin layer of braided copper wire with a magnetic, screened/
armoured intermediate layer.
f.
Cable that runs in copper tube or steel tube.
g.
Lead cable with 1.1 mm wall thickness.
MG.33.BC.02 - VLT
®