FC 300 Design Guide
NB!
The selection in par. 8-51
Bit 05, Hold frequency output/Use ramp
When bit 05 = "0", the current output frequency is being maintained even if the reference value is modified.
When bit 05 = "1", the frequency converter can perform its regulating function again; operation occurs according to the respective reference value.
Bit 06, Ramp stop/Start
Normal ramp stop using the ramp times of the actual ramp as selected. In addition, activation of the output relay 01 or 04 if the output frequency is 0
Hz if Relay 123 has been selected in par. 5-40
other start conditions are satisfied.
NB!
The selection in par. 8-53
Bit 07, No function/Reset
Reset after switching off.
Acknowledges event in fault buffer.
When bit 07 = "0", no reset occurs.
When there is a slope change of bit 07 to "1", a reset occurs after switching off.
Bit 08, Jog 1 OFF/ON
Activation of the pre-programmed speed in par. 8-90
Bit 09, Jog 2 OFF/ON
Activation of the pre-programmed speed in par. 8-91
Bit 10, Data invalid/valid
Is used to tell the frequency converter whether the control word is to be used or ignored. Bit 10 = "0" causes the control word to be ignored, Bit 10 =
"1" causes the control word to be used. This function is relevant, because the control word is always contained in the telegram, regardless of which type
of telegram is used, i.e. it is possible to turn off the control word if you do not wish to use it in connection with updating or reading parameters.
Bit 11, No function/Slow down
Is used to reduce the speed reference value by the amount given in par. 3-12
the reference value occurs. When bit 11 = "1", the reference value is reduced.
Bit 12, No function/Catch up
Is used to increase the speed reference value by the amount given in par. 3-12
When bit 12 = "0", no modification of the reference value occurs.
When bit 12 = "1", the reference value is increased.
If both - slowing down and accelerating - are activated (bit 11 and 12 = "1"), slowing down has priority, i.e. the speed reference value will be reduced.
Quick Stop Select
determines how bit 04 is linked with the corresponding function of the digital inputs.
Function Relay
. Bit 06 = "0" leads to a stop. When bit 06 = "1", the frequency converter can start if the
Start Select
determines how bit 06 is linked with the corresponding function of the digital inputs.
Bus Jog 1 Speed
. JOG 1 is only possible if bit 04 = "0" and bit 00 - 03 = "1".
Bus Jog 2 Speed
. JOG 2 is only possible if bit 04 = "0" and bit 00 - 03 = "1".
Catch up/slow Down Value
Catch up/slow Down Value
MG.33.BC.02 - VLT
®