Specifications
7.10 Acoustic Noise Ratings
50% fan speed
Enclosure size
[dBA]
A1
A2
A3
A4
A5
B1
B2
B4
C1
C2
C4
D3h
Table 7.60 Acoustic Noise Ratings
Values are measured 1 m (3.3 ft) from the unit.
7.11 Selected Options
®
7.11.1 VLT
General Purpose I/O Module
MCB 101
MCB 101 is used for extension of digital and analog inputs
and outputs.
®
7.11.2 VLT
Relay Card MCB 105
The relay option MCB 105 includes three pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data
Maximum terminal load (AC-1)
Maximum terminal load (AC-15 )
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load (DC)
Maximum switching rate at rated load/min load
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately, the kit
includes
•
Relay module MCB 105
•
Enlarged LCP fixture and enlarged terminal cover
•
Label for covering access to switches S201, S202
and S801
•
Cable strips for fastening cables to relay module
MG20N622
Design Guide
Full fan speed
[dBA]
51
60
51
60
51
60
51
60
54
63
61
67
58
70
52
62
52
62
55
65
56
71
58
71
1)
(resistive load)
(inductive load @ cosφ 0.4)
1)
1)
(resistive load)
1)
(inductive load)
Danfoss A/S © 09/2014 All rights reserved.
Fit MCB 101 into slot B of the adjustable frequency drive.
Contents:
•
MCB 101 option module
•
Extended fixture for LCP
•
Terminal cover
MCB 101
General Purpose I/O
SW. ver. XX.XX
X30/
1
2
3
4
5
6
Figure 7.2 MCB 101 Option
FC Series
B slot
Code No. 130BXXXX
7
8
9
10
11
12
240 V AC 2 A
240 V AC 0.2 A
24 V DC 1 A
24 V DC 0.1 A
5 V 10 mA
-1
-1
6 minimum
/20 s
185
7
7