Danfoss FC 300 Design Manual page 85

0,25 kwt - 1,2 mwt
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
AutomationDrive FC 300, P7K5T2
Cable
Mains
length [m]
voltage [V]
36
240
136
240
150
240
AutomationDrive FC 300, P11KT2
Cable
Mains
length [m]
voltage [V]
30
240
100
240
150
240
AutomationDrive FC 300, P15KT2
Cable
Mains
length [m]
voltage [V]
36
240
136
240
150
240
AutomationDrive FC 300, P18KT2
Cable
Mains
length [m]
voltage [V]
36
240
136
240
150
240
AutomationDrive FC 300, P22KT2
Cable
Mains
length [m]
voltage [V]
15
240
50
240
150
240
AutomationDrive FC 300, P30KT2
Cable
Mains
length [m]
voltage [V]
30
240
100
240
150
240
AutomationDrive FC 300, P37KT2
Cable
Mains
length [m]
voltage [V]
30
240
100
240
150
240
Upeak
Rise time [μsec]
[kV]
0.264
0.624
0.536
0.596
0.568
0.568
Rise time
Upeak
[μsec]
[kV]
0.556
0.650
0.592
0.594
0.708
0.587
Rise time
Upeak
[μsec]
[kV]
0.244
0.608
0.568
0.580
0.720
0.574
Rise time
Upeak
[μsec]
[kV]
0.244
0.608
0.568
0.580
0.720
0.574
Rise time
Upeak
[μsec]
[kV]
0.194
0.626
0.252
0.574
0.488
0.538
Rise time
Upeak
[μsec]
[kV]
0.300
0.598
0.536
0.566
0.776
0.546
Rise time
Upeak
[μsec]
[kV]
0.300
0.598
0.536
0.566
0.776
0.546
MG.33.BC.02 - VLT
®
is a registered Danfoss trademark
4 AutomationDrive FC 300 Selection
du/dt [kV/μsec]
1.890
0.889
0.800
du/dt
[kV/μsec]
0.935
0.802
0.663
du/dt
[kV/μsec]
1.993
0.816
0.637
du/dt
[kV/μsec]
1.993
0.816
0.637
du/dt
[kV/μsec]
2.581
1.822
0.882
du/dt
[kV/μsec]
1.594
0.844
0.562
du/dt
[kV/μsec]
1.594
0.844
0.562
4
85

Advertisement

Table of Contents
loading

Table of Contents