Danfoss FC 300 Design Manual page 242

0,25 kwt - 1,2 mwt
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

11 RS-485 Installation and Set-up
Coil Number
1-16
17-32
33-48
49-64
65
66-65536
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Frequency converter control word (FC profile)
11
Register Number
00001-00006
00007
00008
00009
00010-00990
01000-01990
02000-02990
03000-03990
04000-04990
...
49000-49990
50000
50010
...
50200
50210
* Used to specify the index number to be used when accessing an indexed parameter.
242
Description
Frequency converter control word (see table below)
Frequency converter speed or set-point reference Range 0x0 – 0xFFFF (-200% ...
~200%)
Frequency converter status word (see table below)
Open loop mode: Frequency converter output frequency Closed loop mode: Frequency
converter feedback signal
Parameter write control (master to slave)
0 =
Parameter changes are written to the RAM of the frequency converter
1 =
Parameter changes are written to the RAM and EEPROM of the frequen-
cy converter.
Reserved
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
Description
Reserved
Last error code from an FC data object interface
Reserved
Parameter index*
000 parameter group (parameters 001 through 099)
100 parameter group (parameters 100 through 199)
200 parameter group (parameters 200 through 299)
300 parameter group (parameters 300 through 399)
400 parameter group (parameters 400 through 499)
...
4900 parameter group (parameters 4900 through 4999)
Input data: Frequency converter control word register (CTW).
Input data: Bus reference register (REF).
...
Output data: Frequency converter status word register (STW).
Output data: Frequency converter main actual value register (MAV).
MG.33.BC.02 - VLT
Coil
0
33
Control not ready
34
Frequency converter not
ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of freq. range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Frequency converter status word (FC profile)
Holding registers
®
is a registered Danfoss trademark
FC 300 Design Guide
Signal Direction
Master to slave
Master to slave
Slave to master
Slave to master
Master to slave
1
Control ready
Frequency converter ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning

Advertisement

Table of Contents
loading

Table of Contents