Danfoss FC 300 Design Manual page 71

0,25 kwt - 1,2 mwt
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Mains Supply 3 x 525- 690 VAC
AutomationDrive FC
302
High/ Normal Load*
Typical Shaft output at
550 V [kW]
Typical Shaft output at
575 V [HP]
Typical Shaft output at
690 V [kW]
Enclosure IP21, 55
Output current
Continuous
(3 x 525-550 V) [A]
Intermittent (60 sec
overload)
(3 x 525-550 V) [A]
Continuous
(3 x 551-690 V) [A]
Intermittent (60 sec
overload)
(3 x 551-690 V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Continuous KVA
(at 690 V) [KVA]
Max. input current
Continuous
(at 550 V ) [A]
Continuous
(at 575 V ) [A]
Max. cable size, mains,
motor, load share and
brake [mm
Max. external mains
fuses [A]
Estimated power loss
at rated max. load [W]
4)
Weight,
enclosure IP21, IP 55
[kg]
4)
Efficiency
* High overload = 150% torque during 60 s, Normal overload = 110% torque during 60 s
P30K
HO
NO
22
30
30
40
30
37
C2
36
43
54
47.3
34
41
51
45.1
34.3
41.0
33.9
40.8
40.6
49.0
36
49
54
53.9
2
(AWG)]
80
1
480
0.98
MG.33.BC.02 - VLT
®
is a registered Danfoss trademark
4 AutomationDrive FC 300 Selection
P37K
P45K
HO
NO
HO
NO
30
37
37
45
40
50
50
60
37
45
45
55
C2
C2
43
54
54
65
64.5
59.4
81
71.5
41
52
52
62
61.5
57.2
78
68.2
41.0
51.4
51.4
61.9
40.8
51.8
51.8
61.7
49.0
62.1
62.1
74.1
49
59
59
71
72
64.9
87
78.1
35 (1/0)
100
125
592
720
65
0.98
0.98
P75K
P55K
HO
NO
HO
NO
45
55
55
75
60
75
75
100
55
75
75
90
C2
C2
65
87
87
105
97.5
95.7
130.5
115.5
62
83
83
100
93
91.3
124.5
110
61.9
82.9
82.9
100.0
61.7
82.7
82.7
99.6
74.1
99.2
99.2
119.5
71
87
87
99
105
95.7
129
108.9
160
160
880
1200
0.98
0.98
4
71

Advertisement

Table of Contents
loading