FC 300 Design Guide
11.8.9 How to Control the Frequency Converter
This section describes codes which can be used in the function and data fields of a Modbus RTU message. For a complete description of all the message
Modbus RTU Message Framing Structure.
fields please refer to the section
11.8.10 Function Codes Supported by Modbus RTU
Modbus RTU supports use of the following function codes in the function
field of a message:
Function
Function Code
Diagnostics
8
11.8.11 Modbus Exception Codes
For a full explanation of the structure of an exception code response, please refer to the section
Code
Name
1
Illegal function
2
Illegal data address
3
Illegal data value
4
Slave device failure
Function
Read coils
Read holding registers
Write single coil
Write single register
Write multiple coils
Write multiple registers
Get comm. event counter
Report slave ID
Sub-function code
1
2
10
11
12
13
14
Modbus Exception Codes
Meaning
The function code received in the query is not an allowable action for the server (or slave). This may
be because the function code is only applicable to newer devices, and was not implemented in the unit
selected. It could also indicate that the server (or slave) is in the wrong state to process a request of
this type, for example because it is not configured and is being asked to return register values.
The data address received in the query is not an allowable address for the server (or slave). More
specifically, the combination of reference number and transfer length is invalid. For a controller with
100 registers, a request with offset 96 and length 4 would succeed, a request with offset 96 and length
5 will generate exception 02.
A value contained in the query data field is not an allowable value for server (or slave). This indicates
a fault in the structure of the remainder of a complex request, such as that the implied length is
incorrect. It specifically does NOT mean that a data item submitted for storage in a register has a value
outside the expectation of the application program, since the Modbus protocol is unaware of the sig-
nificance of any particular value of any particular register.
An unrecoverable error occurred while the server (or slave) was attempting to perform the requested
action.
MG.33.BC.02 - VLT
®
is a registered Danfoss trademark
11 RS-485 Installation and Set-up
Function Code
1 hex
3 hex
5 hex
6 hex
F hex
10 hex
B hex
11 hex
Sub-function
Restart communication
Return diagnostic register
Clear counters and diagnostic register
Return bus message count
Return bus communication error count
Return bus exception error count
Return slave message count
Modbus RTU Message Framing Structure, Function Field.
11
243