Danfoss FC 300 Design Manual page 228

0,25 kwt - 1,2 mwt
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

10 Options and Accessories
IEC 60755 Type B device monitors AC, pulsed DC, and pure DC ground fault currents
LED bar graph indicator of the ground fault current level from 10–100% of the set-point
Fault memory
TEST / RESET button
Insulation Resistance Monitor (IRM)
Monitors the insulation resistance in ungrounded systems (IT systems in IEC terminology) between the system phase conductors and ground. There is
an ohmic pre-warning and a main alarm set-point for the insulation level. Associated with each set-point is an SPDT alarm relay for external use. Note:
only one insulation resistance monitor can be connected to each ungrounded (IT) system.
Integrated into the drive's safe-stop circuit
LCD display of the ohmic value of the insulation resistance
Fault Memory
INFO, TEST, and RESET buttons
IEC Emergency Stop with Pilz Safety Relay
Includes a redundant 4-wire emergency-stop push-button mounted on the front of the enclosure and a Pilz relay that monitors it in conjunction with the
drive's safe-stop circuit and the mains contactor located in the options cabinet.
Manual Motor Starters
Provide 3-phase power for electric blowers often required for larger motors. Power for the starters is provided from the load side of any supplied contactor,
circuit breaker, or disconnect switch. Power is fused before each motor starter, and is off when the incoming power to the drive is off. Up to two starters
are allowed (one if a 30A, fuse-protected circuit is ordered). Integrated into the drive's safe-stop circuit.
Unit features include:
Operation switch (on/off)
Short-circuit and overload protection with test function
Manual reset function
30 Ampere, Fuse-Protected Terminals
3-phase power matching incoming mains voltage for powering auxiliary customer equipment
10
Not available if two manual motor starters are selected
Terminals are off when the incoming power to the drive is off
Power for the fused protected terminals will be provided from the load side of any supplied contactor, circuit breaker, or disconnect switch.
24 VDC Power Supply
5 amp, 120 W, 24 VDC
Protected against output over-current, overload, short circuits, and over-temperature
For powering customer-supplied accessory devices such as sensors, PLC I/O, contactors, temperature probes, indicator lights, and/or other
electronic hardware
Diagnostics include a dry DC-ok contact, a green DC-ok LED, and a red overload LED
External Temperature Monitoring
Designed for monitoring temperatures of external system components, such as the motor windings and/or bearings. Includes eight universal input modules
plus two dedicated thermistor input modules. All ten modules are integrated into the drive's safe-stop circuit and can be monitored via a fieldbus network
(requires the purchase of a separate module/bus coupler).
Universal inputs (8)
Signal types:
RTD inputs (including Pt100), 3-wire or 4-wire
Thermocouple
Analog current or analog voltage
Additional features:
One universal output, configurable for analog voltage or analog current
Two output relays (N.O.)
Dual-line LC display and LED diagnostics
Sensor lead wire break, short-circuit, and incorrect polarity detection
Interface setup software
228