Emc Test Results - Danfoss FC 300 Design Manual

0,25 kwt - 1,2 mwt
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide

3.5.2 EMC Test Results

The following test results have been obtained using a system with a frequency converter (with options if relevant), a screened control cable, a
control box with potentiometer, as well as a motor and motor screened cable.
RFI filter type
Standards and requirements EN 55011
EN/IEC 61800-3
H1
AutomationDrive FC 301:
AutomationDrive FC 302:
H2
AutomationDrive FC 301/
AutomationDrive FC 302:
11-22 kW 525-690 V
30-75 kW 525-690 V
37-1000 kW 525-690 V
H3
AutomationDrive FC 301:
H4
AutomationDrive FC 302
11-22 kW 525-690 V
30-75 kW 525-690 V
37-315 kW 525-690 V
Hx
AutomationDrive FC 302
0.75-75 kW 525-600 V
Table 3.1: EMC Test Results (Emission, Immunity)
1) Frame size B
2) Frame size C
3) Frame size D, E and F
HX, H1, H2 or H3 is defined in the type code pos. 16 - 17 for EMC filters
HX - No EMC filters built in the frequency converter (600 V units only)
H1 - Integrated EMC filter. Fulfil EN 55011 Class A1/B and EN/IEC 61800-3 Category 1/2
H2 - No additional EMC filter. Fulfil EN 55011 Class A2 and EN/IEC 61800-3 Category 3
H3 - Integrated EMC filter. Fulfil EN 55011 class A1/B and EN/IEC 61800-3 Category 1/2 (Frame size A1 only)
H4 - Integrated EMC filter. Fulfil EN 55011 class A1 and EN/IEC 61800-3 Category 2
Class B
Housing,
trades and
light industries
Category C1
First environ-
ment Home
and office
0-37 kW 200-240 V
10 m
0-75 kW 380-480 V
10 m
0-37 kW 200-240 V
50 m
0-75 kW 380-480 V
50 m
0-3.7 kW 200-240 V
No
5.5-37 kW 200-240 V
No
0-7.5 kW 380-480 V
No
11-75 kW 380-480 V
No
90-800 kW 380-500 V
No
1)
No
2)
No
3)
No
0-1.5 kW 200-240 V
2.5 m
0-1.5 kW 380-480 V
2.5 m
90-800 kW 380-500 V
No
1)
No
2)
No
3)
No
-
MG.33.BC.02 - VLT
®
is a registered Danfoss trademark
3 Introduction to AutomationDrive FC 300
Conducted emission
Class A
Class A
Group 1
Group 2
Housing, trades
Industrial
Industrial envi-
and light indus-
environment
ronment
Category
Category C3
C2
Second envi-
First environ-
ronment In-
ment Home and
ment Home
dustrial
and office
50 m
75 m
50 m
75 m
150 m
150 m
150 m
150 m
No
5 m
No
25 m
No
5 m
No
25 m
No
150 m
No
25 m
No
25 m
No
150 m
25 m
50 m
25 m
50 m
150 m
150 m
100 m
100 m
150 m
150 m
30 m
150 m
-
-
Radiated emission
Class B
Class A Group 1
Industrial environ-
ment
tries
Category C1
Category C2
First environ-
First environment
Home and office
office
No
Yes
No
Yes
No
Yes
No
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
No
-
-
3
39

Advertisement

Table of Contents
loading

Table of Contents