8 Electrical Installation

8.6.3 Control Terminals

Control Terminals, AutomationDrive FC 301
Drawing reference numbers:
1.
8 pole plug digital I/O.
2.
3 pole plug RS485 Bus.
3.
6 pole analog I/O.
4.
USB Connection.
Control Terminals, AutomationDrive FC 302
Drawing reference numbers:
1.
10 pole plug digital I/O.
2.
3 pole plug RS485 Bus.
3.
6 pole analog I/O.
4.
USB Connection.
8

8.6.4 Switches S201, S202, and S801

Switches S201 (A53) and S202 (A54) are used to select a current (0-20 mA) or a voltage (-10 to 10 V) configuration of the analog input terminals 53 and
54 respectively.
Switch S801 (BUS TER.) can be used to enable termination on the RS-485 port (terminals 68 and 69).
Diagram showing all electrical terminals
See drawing
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
When changing the function of S201, S202 or S801 be careful not to use force for the switch over. It is recommended to remove the
LCP fixture (cradle) when operating the switches. The switches must not be operated with power on the frequency converter.
180
Illustration 8.36: Control terminals (all frame sizes)
Electrical Installation.
in section
MG.33.BC.02 - VLT
®
is a registered Danfoss trademark
FC 300 Design Guide