Electrical Installation
4
4
1 Routing path for the control card wiring, inside the frequency
converter enclosure.
Illustration 4.8 Control Card Wiring Path for Frame Size F18
4.8.2 Access to Control Terminals
All terminals to the control cables are located beneath the
LCP (both filter and frequency converter LCPs). They are
accessed by opening the door of the unit.
36
Operating Instructions
4.8.3 Electrical Installation, Control
To connect the cable to the terminal:
1
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
Terminals
1.
Strip insulation by about 9–10 mm
Illustration 4.9 Length to Strip the Insulation
2.
Insert a screwdriver (max. 0.4x2.5 mm) in the
square hole.
3.
Insert the cable in the adjacent circular hole.
Illustration 4.10 Inserting the Cable in the Terminal Block
4.
Remove the screwdriver. The cable is now
mounted in the terminal.
9 - 10 mm
(0.37 in)
MG21B202