3. Check the server airflow. Make sure that nothing is blocking the air from coming into or
preventing the air from exiting the server.
80010901-1406ffff : Numeric sensor [NumericSensorElementName] going high (upper critical)
has asserted. (DIMM GH VR Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109011406ffff or 0x800109011406ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0494
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
80010901-2d01ffff : Numeric sensor [NumericSensorElementName] going high (upper critical)
has asserted. (PCH Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109012d01ffff or 0x800109012d01ffff
Severity
Error
Serviceable
Yes
Appendix A. Integrated management module II (IMM2) error messages
369