IDM Unit Fault Diagnosis

Table 22 - Exception/Fault Behavior
IPIM Display
IDM Status
(RSLogix Drive Fault)
Indicator
E04 – Motor Overtemp
Flashing
Red
(MotorOvertempFault)
E05 – Power Fault
Flashing
Red
(DriveOvercurrentFault)

Logix Controller/IDM Unit Fault Behavior

These RSLogix 5000 fault actions are configurable from the Axis Properties
dialog box, Fault Actions tab.
Table 21 - Fault Action Definitions
Fault Action
Shutdown
Disable Drive
Stop Motion
Status Only
Only selected faults are programmable.
programmable RSLogix Fault Action. Faults that do not have a programmable
fault action will have the Shutdown action described in
Figure 38 - RSLogix 5000 Axis Properties - Fault Actions Tab
Drive Fault Action/Attribute for
IDM Overtemp fault (E04).
Potential Cause
Excessive IDM unit temperature.
Operation above the IGBT
instantaneous current rating or IPIM
module power supply undervoltage.
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Troubleshooting the Kinetix 6000M System
Definition
Axis is disabled as defined in
Table
22. In addition, the axis in Logix enters the Shutdown
state, which disables any axes that are using this axis as a camming or gearing master. The
AxisHomedStatus tag for the faulted axis is cleared. Shutdown is the most severe action to a
fault and it is usually reserved for faults that could endanger the machine or operator if
power is not removed as quickly as possible.
The axis is disabled as defined in the
Table
The axis decelerates at the maximum deceleration rate (set in RSLogix 5000 software>Axis
Properties>Dynamics tab). Once the axis has come to a stop, the servo loops remain enabled
but no further motion can be generated until the fault is reset. This is the gentlest stopping
mechanism in response to a fault. It is usually used for less severe faults.
System continues to operate. Status is displayed on the IPIM module.
Table 22
Possible Solution
• Lower ambient temperature, increase IDM
unit cooling.
• Operate within the instantaneous power
rating.
• Reduce acceleration rates.
• If fault persists, replace IDM unit.
22.
indicates which faults have a
Table
21.
RSLogix
Programmable
Fault Action
Fault Behavior
Yes
Decel/Disable
No
Coast/Disable/
Open Contactor
Enable