Minimum Clearance Requirements - Allen-Bradley Kinetix 6000M User Manual

Integrated drive-motor system
Table of Contents

Advertisement

Table 7 - Power Dissipation Specifications - Percent of DC Bus Current
Power Dissipation as % of DC Bus Current Output Rating
Watts
20%
40%
60%
2
7
14
(1) x is percent of DC bus current output rating: any value between 0.0 and 1.0.
Table 8 - Power Dissipation Specifications - Percent of IPIM Module Control Power
Power Dissipation as % of IPIM Module Control
Control Power Input
Frequency
Voltage
Hz
AC
20%
120V
22
50
240V
34
120V
23
60
240V
38
(1) x is percent of IPIM module control power output rating: any value between 0.0 and 1.0.

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your IDM unit.
Figure 7
illustrates minimum clearance requirements for proper airflow and
installation:
• Additional clearance is required for the cables and wires connected to the
top and front of the module.
• Additional clearance left and right of the power rail is required when the
module is mounted adjacent to noise sensitive equipment or clean
wireways.
Table 9 - Minimum Cabinet Depth
Cat. No.
2094-SEPM-B24-S
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Planning the Kinetix 6000M System Installation
80%
100%
Heat Dissipation Formula
25
38
Y = 33.95x
Power Output Rating
Watts
40%
60%
80%
100%
29
38
48
61
42
52
63
76
27
32
39
46
49
62
76
92
Cabinet Depth, Min
272 mm (10.7 in.)
Chapter 2
(1)
2
+ 3.18x
(1)
Heat Dissipation Formulas
2
Y = 23.76x
+ 20.73x + 16.54
2
Y = 18.56x
+ 30.19x + 27.41
2
Y = 14.57x
+ 11.40x + 20.01
2
Y = 19.63x
+ 43.22x + 28.75
25