IPIM Module Firmware
Upgrade
8. Click OK.
The new Ethernet driver appears under Configured Drivers.
9. Click Close.
10. Minimize the RSLinx application dialog box.
The IPIM module will not accept a firmware upgrade request when it has an
IMPORTANT
active CIP I/O connection.
An active CIP I/O connection exists when the IPIM module has been integrated
into the I/O configuration tree in RSLogix 5000 software. The IPIM module
only accepts a firmware upgrade request when the connection is inhibited. The
connection can be inhibited from I/O Configuration>Enet Module>IPIM
Module Properties>Connection tab (see below). The IPIM module always
accepts a firmware upgrade request if it is connected to a Logix Ethernet module,
but has not been integrated in the I/O configuration tree.
Additionally, the firmware upgrade can be accomplished by disconnecting the
IPIM module from the Logix Ethernet module and establishing a direct
connection to a computer with ControlFlash software.
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Upgrading the Kinetix 6000M System Firmware
Appendix C
117