Chapter 5
Connecting the Kinetix 6000M System

How to Bypass an IDM Unit

58
Figure 24 - Hybrid Cable Installed
Hybrid Cable

Network Cable

The IDM system network is routed by using 2090-CNSxPxS-AAxx cables. A
2090-CNSSPRS-AAxx or 2090-CNSSPSS-AAxx cable is required for
connection to the IPIM module.
2090-CNSSPRS-AAxx
(1)
2090-CNSRPSS-AAxx
(1)
2090-CNSRPRS-AAxx
2090-CNSSPSS-AAxx
(1) Not for connection to an IPIM module.
When installing network cables, torque the connector plug to 0.8...1.2 N•m
(7.1...10.6 lb•in) to fully seat the contacts and secure the connection.
A 2090-CCPPS8S coupler cable joins two hybrid cables to bypass an IDM unit
or extend the length of a cable. This can be desired when performing
maintenance on a unit or to simply extend a hybrid cable. IDM to IDM cable
lengths should not exceed 25 m (82.0 ft) during normal operation when a
coupling cable is used.
The IDM network cables can be joined to together without the need of a coupler
to bypass an IDM unit or extend network cables.
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Hybrid Cable DC Bus Connector
Hybrid Cable Communication
Signals Connector
42+
42+
42-
42-
SH2
SH2
CN-
CN-
CN+
CN+
OUT
OUT
RTN
RTN
SH3
SH3
SE1
SE1
SE-
SE-
SE2
SE2