Interpret Status Indicators

90
When a fault condition is detected, the appropriate status indicator will
illuminate (IDM unit or IPIM module) and the IPIM module will annunciate
the fault on its front panel display. Refer to
descriptions and
Figure 37

IPIM Module Status Indicators

IPIM module fault descriptions, types and actions start on
Figure 36 - IPIM Display and Status Indicators
IPIM
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
Info
Tools
Control Bus
Module Status
Network Status
DC Bus
Port 1
Port 2
Indicator
Indication
Control
Status of the
Off
Bus
Control Bus
Solid Green
Solid Red
Module
IPIM Module
Off
Status
Status
Flashing Green
Solid Green
Flashing Red
Solid Red
Alternating Green/Red
Network
Network Status
Off
Status
Flashing Green
Solid Green
Flashing Red
Solid Red
Alternating Green/Red
DC Bus
Status of the DC
Off
Bus
Flashing Green
Solid Green
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Figure 36
for IDM unit indicators.
Control Bus
Module Status
Network Status
DC Bus
Port 1
Port 2
Description
Control bus is not present
Control bus is present
A fault has occurred
Power is not applied to the module
Module is in Standby mode - configuration may be required
Module is operating correctly
A recoverable fault has occurred
An unrecoverable fault has occurred
Self-test mode during powerup
Not powered or no IP address
No connections, but an IP address has been obtained
An established connection exists
A connection has timed out
Duplicate IP is present
Self-test mode during powerup
DC Bus is not present
DC bus is present and all IDM units are disabled
DC bus is present and at least one IDM unit is enabled