2.7.22 APS-PRIM-SEC-MISM
Step 2
If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC 1 800 553-2447.
2.7.22 APS-PRIM-SEC-MISM
The Optimized 1+1 APS Primary Section Mismatch condition occurs on OC-N cards in an optimized
1+1 protection system if there is a mismatch between the primary section of the local node facility and
the primary section of the remote-node facility.
Clear the APS-PRIM-SEC-MISM Alarm
Ensure that the local node and remote-node ports are correctly provisioned the same way. For more
Step 1
information about optimized 1+1 configurations, refer to the "Turn Up Node" chapter in the
Cisco ONS 15454 Procedure Guide.
If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
Step 2
for more information or call Cisco TAC 1 800 553-2447.
2.7.23 AS-CMD
The Alarms Suppressed by User Command condition applies to the network element (NE object),
backplane, a single card, or a port on a card. It occurs when alarms are suppressed for that object and its
subordinate objects. For example, suppressing alarms on a card also suppresses alarms on its ports.
For more information about suppressing alarms, refer to the "Manage Alarms" chapter in the
Note
Cisco ONS 15454 Procedure Guide.
Clear the AS-CMD Condition
For all nodes, in node view, click the Conditions tab.
Step 1
Click Retrieve. If you have already retrieved conditions, look under the Object column and Eqpt Type
Step 2
column and note what entity the condition is reported against, such as a port, slot, or shelf.
Cisco ONS 15454 Troubleshooting Guide, R8.5
2-46
Default Severity: Minor (MN), Non-Service Affecting (NSA)
SONET Logical Object: OCN
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
SONET Logical Objects: BPLANE, CEMR, CE1000, CE100T, DS1, DS3, E1, E1000F, E100T,
EC1, EQPT, FCMR, G1000, GFP-FAC, ML1000, ML100T, MLFX, NE, OCN, PWR
DWDM Logical Objects: 2R, AOTS, ESCON, FC, GE, ISC, OCH, OMS, OTS, PPM, SHELF,
TRUNK
If the condition is reported against a slot and card, alarms were either suppressed for the entire card
or for one of the ports. Note the slot number and continue with
Chapter 2
Alarm Troubleshooting
Step